Joerger Logo

MODEL
OR-2, OR-3, OR-4

 

16, BIT SELECTABLE, REGISTER
WITH ISOLATED OUTPUTS

 

FEATURES:

  • 16 BIT REGISTER WITH REED RELAY, OPTICAL ISOLATED OR TTL OUTPUTS
  • EACH CHANNEL CAN BE SELECTIVELY SET OR RESET INDIVIDUALLY OR
    SIMULTANEOUSLY
  • REGISTER CAN BE REREAD TO VERIFY ITS CONTENTS
  • VISUAL DISPLAY OF REGISTER CONTENTS

 

APPLICATIONS:

  • REMOTE CONTROL APPLICATIONS
  • PROGRAMMABLY SET OR RESET EACH INDIVIDUAL CHANNEL OR ALL 16
    CHANNELS AT ONE TIME
  • PROVIDES CHOICE OF OPTICAL, REED RELAY OR TTL OUTPUTS WHICH WILL
    BEST SATISFY A PARTICULAR APPLICATION

 

JOERGER ENTERPRISES, INC. offers this series of isolated output modules. The MODELS OR-2, OR-3, and the OR-4 each contains 16 individually programmable output channels. They provide the user with the ability to individually set or reset any individual channel or set and reset all 16 channels simultaneously. To add to their versatility they also offer a variety of outputs. The Model OR-2 output is 16 form A type reed relays as standard output drivers with dual form A’s or form C’s available as options. The MODEL OR-3 offers 16 optically isolated outputs in a common emitter configuration with separate power and ground outputs. The MODEL OR-4 offers standard TTL outputs with open collector outputs optional. We believe the flexible programming and chose of outputs make this series of modules quite useful in many system requirements. To visually verify the contents of the register 16 front panel LED’s are provided.

 

SPECIFICATIONS: (for each channel)

MODEL OR-2 Provides form A reed relays for all 16 channels, with dual form A’s or form C’s available as options
Relay contacts are rated at 500ma, 100v and 10watts
MODEL OR-3 Provides optically isolated outputs for all 16 channels. Each output is in a common emitter configuration and has a separate power and ground input
Rated at 30v, 200ma
MODEL OR-4 Provides standard TTL outputs with open collector outputs optional
Rated at: Logic "1" .5v sinking 50ma, Logic "0" 2.4v minimum

CAMAC COMMANDS:

COMMAND

Q

FUNCTION
00

1

Reads contents of register on to Read lines R1-16
90 Resets complete register
120 Sets complete register to "1"
160

1

Overwrites complete register with data from Write lines, W1-16
180

1

Selectively sets any bits in the register whose W line is at a logic "1"
210

1

Selectively resets any bits in the register whose W line is at a logic "1"
Z(S2) +
POWER UP
Resets module
Q A Q=1 is generated for 00, 160, 180 and 210
X All valid commands generate X=1
CONNECTORS: Cannon 2DB52P, mating connector Cannon 2DB52S
TEMPERATURE RANGE: 0° C to 50° C

INDICATORS:

"N" module addressed
"DATA" displays contents of the 16 bit data register
POWER REQUIREMENTS: +6v, 400ma
SIZE: #1 CAMAC module

 

JOERGER ENTERPRISES, INC 166 Laurel Road, East Northport, NY 11731 USA

1-631-757-6200 (Fax 1-631-757-6201) www.joergerinc.com

[HOME] [CAMAC] [VME] [NIM]